EasyManuals Logo

Carrier VECTOR 1550 Series User Manual

Carrier VECTOR 1550 Series
270 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #145 background imageLoading...
Page #145 background image
62-61753-21
7-29
Alarm
NO.
Steps
ALARM / CAUSE
CORRECTIVE ACTION
39 CHECK ENGINE RPM
TRIGGER-ON:
"Check Engine RPM Sensor" alarm not active (if so, refer to alarm 130 first) and:
engine speed is less than 1350 or greater than 2050 for 5 minutes or engine speed drops to less than
1300 for 5 seconds after the engine speed has been greater than 1350 for 3 seconds.
UNIT CONTROL: Engine operation: alarm only or (if configured for shutdown) engine and unit
shutdown and alarm.
Standby operation: Will not activate in standby.
RESET CONDITION: Auto Reset if engine speed is greater than 1350 and less than 2000 for
5 minutes or after 15 minutes if the engine has been shutdown or change unit to standby operation or
alarm may be manually reset via keypad or by turning the unit off, then back on again.
NOTE: Follow the steps below until a problem is found. Once a repair or correction has been made, the active
alarm should clear itself (refer to reset condition above). Operate the unit through the appropriate modes to see if
any active alarm occurs. Continue with the steps below as necessary.
1
Check Model Number
a. Verify that the model number on
the Unit Data label matches the
model number shown in the micro-
processor Unit Data list.
Configure the unit for the correct model number. (Refer
to Section 5.1.1.)
2
Check Engine Fuel System
a. Check fuel tank level.
Must have enough fuel to run engine.
b. Check fuel lines.
Connections are tight and not leaking.
No kinks or sharp bends in the lines.
c. Check fuel screen.
Fuel screen is located in the inlet fitting to the lift pump.
Screen must be clean.
d. Check fuel filters.
Fuel filters must be clean and allow full flow of fuel
through them.
3
Check Engine Air-Intake System
a. Check air filter.
Replace if required.
b. Inspect air intake system.
Hoses & tubes in good condition.
No kinks or restrictions.
4
Force Low Speed operation
a. Using Functional Parameters, set
the Low Speed Start Up Delay to
10 minutes and start unit.
Unit will run in low speed. Speed must be within range
provided above. Adjust speed linkage as needed. Re-
fer to Section 8.4.9
b. Check Speed Relay LED27.
LED27 must be OFF.
5
Check Engine Speed
a. Check actual engine speed using
hand held tachometer.
Refer to Section 2.8 for required speed. Adjust engine
linkage setting as needed. Refer to Section 8.4.9
b. Compare actual low speed with
that shown on display.
Both readings within ± 50 RPM.
Additional steps on the next page.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier VECTOR 1550 Series and is the answer not in the manual?

Carrier VECTOR 1550 Series Specifications

General IconGeneral
BrandCarrier
ModelVECTOR 1550 Series
CategoryRefrigerator
LanguageEnglish

Related product manuals