GE+ ACDC Installation and operation manual v11
51 / 121
Additionally, in the FG mode, each kind of fault has its own parameters to be modified by the
user. These parameters are listed below:
Parameters of
Voltage Dip, Over/Under Voltage
Allowed range of values
Voltage of fundamental harmonics of phases U, V, W 0-200%
0% means 0V
Angle of fundamental harmonics of phases U, V, W 0-360°
Ramp [V/ms] Fade in: 0.1 ≤ Ramp ≤ 1000
Fade out: 0.1 ≤ Ramp ≤ 1000
Ramp Angle [deg/ms] Fade in: 0.01 ≤ Ramp ≤ 1000
Fade out: 0.01 ≤ Ramp ≤ 1000
*The converter will be limited at a maximum voltage of 277V in case the percentage makes the
voltage exceed this value.
Example Voltage Dip: U%=100, V%=50, W%=50; Uº=0, Vº=60, Wº=300
Example Overvoltage 120%