Citrix ADC MPX
Note
Make sure that a power outlet is available for each cable.
If the kit that you received does not fit your rack, contact your Citrix sales representative to order
the appropriate kit.
Transceiver modules are sold separately. Contact your Citrix sales representative to order
transceiver modules for your appliance. Only transceivers supplied by Citrix are supported on
the appliance.
Important
For Brazilian customers, Citrix does not ship a power cable. Use a cable that conforms to the
ABNT NBR 14136:2002 standard.
In addition to the items included in the box with your new appliance, you will need the following items
to complete the installation and initial configuration process.
Ethernet cables for each additional Ethernet port that you will connect to your network.
One available Ethernet port on your network switch or hub for each Citrix ADC Ethernet port you
want to connect to your network.
A computer to serve as a management workstation.
Prepare the site and rack
There are specific site and rack requirements for the Citrix ADC appliance. You must make sure that ad-
equate environmental control and power density are available. Racks must be bolted to the ground,
have suicient airflow, and have adequate power and network connections. Preparing the site and
rack are important steps in the installation process and help ensure a smooth installation.
Site requirements
The appliance should be installed in a server room or server cabinet with the following features:
Environment control
An air conditioner, preferably a dedicated computer room air conditioner (CRAC), capable of
maintaining the cabinet or server room at a temperature of no more than 27 degrees C/80.6
degrees F at altitudes of up to 2100 m/7000 , or 18 degrees C/64.4 degrees F at higher altitudes,
a humidity level no greater than 45 percent, and a dust-free environment.
Power density
Wiring capable of handling at least 4,000 watts per rack unit in addition to power needs for the
CRAC.
© 1999-2019 Citrix Systems, Inc. All rights reserved. 114

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Citrix ADC MPX Series and is the answer not in the manual?

Citrix ADC MPX Series Specifications

General IconGeneral
TypeApplication Delivery Controller
MemoryUp to 256 GB
Power SupplyRedundant
Product SeriesMPX
Ports10/25/40/100 Gbps Ethernet
Operating SystemCitrix ADC
ManagementCitrix ADM
Form FactorRack-mountable

Related product manuals