EasyManuals Logo

ClimateMaster MPC User Manual

ClimateMaster MPC
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #28 background imageLoading...
Page #28 background image
THE SMART SOLUTION FOR ENERGY EFFICIENCY
MPC MultiProtoCol DDC Controls
November 19, 2018
28
Multi Generation Water-to-Air Points Matrix - cont'd
(Read Left to Right Across Spread)
Point Name Type Number
Read/Write
Type Register Type ID NV Name Default Gen 3 Gen 4 Gen 5 Gen 6 Gen 7 Description
BACNet ModBus N2 LON
C1 Cycle Alarm BV 25 R DI 10013 BI 13 Special* NA X X X X X Indicated the Compressor C1 has cycled ON/OFF more than 5 time during 1 hour.
C2 Cycle Alarm BV 26 R DI 10014 BI 14 Special* NA X X X X X Indicated the Compressor C2 has cycled ON/OFF more than 5 time during 1 hour.
AUX Status BV 27 R DI 10015 BI 15 nvpAuxStatus NA X X X X X Indicates the AUX output (W) is OFF/ON.
SF Manual BV 28 R/W DO 12 BO 12 nviSFMan OFF X X X X X Manual Switch to turn Supply FAN (OFF/ ON). Only Works while in Test Mode.
RV Manual BV 29 R/W DO 13 BO 13 nviRVMan OFF X X X X X Manual Switch to turn Reversing Valve (OFF/ ON). Only Works while in Test Mode.
C1 Manual BV 30 R/W DO 14 BO 14 nviC1Man OFF X X X X X Manual Switch to turn Compressor C1 off or ON. Only Works while in Test Mode.
C2 Manual BV 31 R/W DO 15 BO 15 nviC2Man OFF X X X X X Manual Switch to turn Compressor C2 off or ON. Only Works while in Test Mode.
TSTAT Reset BV 33 R/W ADF 28 Coil 29 nviTstatMode OFF X Obsolete Point found only in Gen 5.
AUX Manual BV 32 R/W DO 16 BO 16 nviAuxMan OFF X X X X X Manual switch to turn AUX Ouput (W) "OFF" or "ON". Only works while in Test Mode.
Test Mode BV 34 R/W DO 18 BO 18 nviTestMode OFF X X X X
Network input used to bypass normal operations in order to operate the unit manually,
maximum ON time for Test Mode is 60 Minutes.
Test Mode BV 37 R/W X Manual switch to turn AUX Ouput (W) either "OFF" or "ON".
Test Mode Alarm BV 38 R DI 10025 BI 21 Special* NA X X X X Indicates the unit is still in Test Mode after the test mode timer has expired.
Metric BV 33 R/W DO 21 BO 28 Special* OFF X X X X Network input used to dene inputs and outputs. Celsius- ON / Fahrenheit -Off.
AUX Toggle BV 40 R/W DO 17 BO 17 nviAuxToggle OFF X X X X
Network input used to toggle the auxillary output (W) "ON" and "OFF" Used when AUX
CFG (AV:31) is set to a value of 11.
Unoccupied Deadband
Celsius
AV 46 R/W Float 40017 Data Float 11 Special* 9.44° C X X X X
Creates the Celsius Heating Setpoint using Unoccupied Cooling Setpoint minus current value
when using the Deadband Mode. Minimum value is 1.1° C with default of 9.44° C . DB Mode
(BV:48) must be "ON".
Relative Humidity Setpoint AV 47 R/W Float 59 Data Float 38 nviRHSP 60% X X X
Network input for the Dehumidication Setpoint above which the Auxillary output(W) is activated
when AUX CFG (AV:31) is set to 12 for Humidity Control.
Relative Humidity Deadband AV 48 R/W Float 61 Data Float 39 nviRHDB 5% X X X
Creates Dehumidifcation turn off point using Relative Humidity SP minus the RH current value
when AUX CFG ( AV:31) is set to 12 for Humidity Control.
Relative Humidity Status AV 49 R Float 34 Data Float 40 nvoRHStatus NA X X X Network Output for Space Relative Humidity when using appropriate sensor.
Aux 5 Temp AV 50 R Float 36 Data Float 41 nvoAux5Temp NA X X X
Network Output for Auxillary Temperature 5 when RNET Mode (BV:44) is "ON" and AUX 5 CFG
(BV:47) is set to "ON" for temperature sensor.
Aux 6 Temp AV 51 R Float 38 Data Float 42 nvoAux6Temp NA X X X
Network Output for Auxillary Temperature 6 when RNET Mode (BV:44) is "ON" and AUX 6 CFG
(BV:46) is set to "ON" for temperature sensor.
CO2 Status AV 52 R Float 40 Data Float 43 nvoCO2Status NA X X X Network Output for Space CO2 level when using the appropriate sensor.
VOC Status AV 53 R Float 42 Data Float 44 Special* NA X X X Network Output for Space VOC level when using the appropriate sensor.
CO2 Trip point AV 54 R/W Float 63 Data Float 45 nviCO2Trip 800 PPM X X X
Network Input for CO2 trip point above which the Auxillary Output is activated when AUX CFG
(AV:31) is set to13 for CO2 Control.
VCO Trippoint AV 55 R/W Float 65 Data Float 46 Special* 800 PPM X X X
Network Input for VOC trip point above which the Auxillary Output is activated when AUX CFG
(AV:31) is set to 14 for VOC Control.
FAN Speed Trigger AV 56 R/W Integer 67 Data Int 12 nviFanSpdTrig 75% X X
Network input for Heating or Cooling PID above which the AUX Output (W) turns "ON" when AUX
CFG is set to 5 for Fan Speed Control. Requires eld wired relay for PSC Motors Only.
Airow Fault Counter AV 57 R Integer 44 Data Int 13 Special* 0 X X
Indicates the number of airow faults that have occured since unit startup or resetting the fault
counter via Fault Count Reset (BV:24).
Pump Fault Counter AV 58 R Integer 45 Data Int 14 Special* 0 X X
Indicates the number of pump faults that have occured since unit startup or resetting the fault
counter via Fault Count Reset (BV:24).
Application Type AV 99 R Float 13 Data Float 9 NA NA X X X Factory Use Only.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ClimateMaster MPC and is the answer not in the manual?

ClimateMaster MPC Specifications

General IconGeneral
BrandClimateMaster
ModelMPC
CategoryController
LanguageEnglish