InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp June 2013
267
14.2.1.46 Binary input: Timer block 16
Related FW
3.0
Description
This input is used to disable temporarily the output from the Timer channel
#16.
NOTE:
See also the setpoint TimerChannel 16 and output TimerAct 13-16.
NOTE:
See the chapter Timers for more details about timers.
14.2.1.47 Binary input: ExtValue1 up
Related FW
3.0
Description
While this input is active the value of ExtValue 1 is contiously beeing
increased at the rate of ExtValue1 rate until it reaches ExtValue1HiLim.
NOTE:
If this input is used (configured), the ExtValue 1 can't be written remotely
from a remote terminal using the command ExtValue 1.
14.2.1.48 Binary input: ExtValue1 down
Related FW
3.0
Description
While this input is active the value of ExtValue 1 is contiously beeing
decreased at the rate of ExtValue1 rate until it reaches ExtValue1LoLim.
NOTE:
If this input is used (configured), the ExtValue 1 can't be written remotely
from a remote terminal using the command ExtValue 1.
14.2.1.49 Binary input: ExtValue2 up
Related FW
3.0
Description
While this input is active the value of ExtValue 2 is contiously beeing
increased at the rate of ExtValue2 rate until it reaches ExtValue2HiLim.
NOTE:
If this input is used (configured), the ExtValue 2 can't be written remotely
from a remote terminal using the command ExtValue 2.