InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp June 2013
268
14.2.1.50 Binary input: ExtValue2 down
Related FW
3.0
Description
While this input is active the value of ExtValue 2 is contiously beeing
decreased at the rate of ExtValue2 rate until it reaches ExtValue2LoLim.
NOTE:
If this input is used (configured), the ExtValue 2 can't be written remotely
from a remote terminal using the command ExtValue 2.
14.2.1.51 Binary input: ExtValue3 up
Related FW
3.0
Description
While this input is active the value of ExtValue 3 is contiously beeing
increased at the rate of ExtValue3 rate until it reaches ExtValue3HiLim.
NOTE:
If this input is used (configured), the ExtValue 3 can't be written remotely
from a remote terminal using the command ExtValue 3.
14.2.1.52 Binary input: ExtValue3 down
Related FW
3.0
Description
While this input is active the value of ExtValue 3 is contiously beeing
decreased at the rate of ExtValue3 rate until it reaches ExtValue3LoLim.
NOTE:
If this input is used (configured), the ExtValue 3 can't be written remotely
from a remote terminal using the command ExtValue 3.
14.2.1.53 Binary input: ExtValue4 up
Related FW
3.0
Description
While this input is active the value of ExtValue 4 is contiously beeing
increased at the rate of ExtValue4 rate until it reaches ExtValue4HiLim.
NOTE:
If this input is used (configured), the ExtValue 4 can't be written remotely
from a remote terminal using the command ExtValue 4.