EasyManuals Logo

ComAp InteliLite 4 AMF 20 User Manual

ComAp InteliLite 4 AMF 20
620 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #568 background imageLoading...
Page #568 background image
InteliLite4 AMF20 Global Guide
568
Alarm Type BOC
Alarmlist message BOC Generator > Frequency
Alarm evaluated Generator excited only
Related applications AMF,MRS
Description
This alarm evaluates the generator frequency in the phase L1. The following
setpoints are related to it:
Generator Overfrequency BOC (page 267)
Generator <> Frequency Delay (page 268)
BOC Generator Overfrequency
6 back to List of alarms level 2
Alarm Type BOC
Alarmlist message BOC Generator < Frequency
Alarm evaluated Generator excited only
Related applications AMF,MRS
Description
This alarm evaluates the generator frequency in the phase L1. The following
setpoints are related to it:
Generator Underfrequency BOC (page 268)
Generator <> Voltage Delay (page 266)
BOC Generator Underfrequency
6 back to List of alarms level 2
Alarm Type MP
Alarmlist message No
Alarm evaluated All the time
Related applications AMF,MRS
Description
This alarm evaluates the Mains phase voltage in phases. The following setpoints
are related to it:
Mains Overvoltage (page 272)
Mains Overvoltage Delay (page 276)
Mains L1 Overvoltage
6 back to List of alarms level 2
Alarm Type MP
Alarmlist message No
Alarm evaluated All the time
Related applications AMF,MRS
Description
This alarm evaluates the Mains phase voltage in phases. The following setpoints
are related to it:
Mains Undervoltage (page 274)
Mains Undervoltage Delay (page 276)
Mains L1 Undervoltage

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite 4 AMF 20 and is the answer not in the manual?

ComAp InteliLite 4 AMF 20 Specifications

General IconGeneral
BrandComAp
ModelInteliLite 4 AMF 20
CategoryController
LanguageEnglish

Related product manuals