InteliLite4 AMF20 Global Guide
568
Alarm Type BOC
Alarmlist message BOC Generator > Frequency
Alarm evaluated Generator excited only
Related applications AMF,MRS
Description
This alarm evaluates the generator frequency in the phase L1. The following
setpoints are related to it:
Generator Overfrequency BOC (page 267)
Generator <> Frequency Delay (page 268)
BOC Generator Overfrequency
6 back to List of alarms level 2
Alarm Type BOC
Alarmlist message BOC Generator < Frequency
Alarm evaluated Generator excited only
Related applications AMF,MRS
Description
This alarm evaluates the generator frequency in the phase L1. The following
setpoints are related to it:
Generator Underfrequency BOC (page 268)
Generator <> Voltage Delay (page 266)
BOC Generator Underfrequency
6 back to List of alarms level 2
Alarm Type MP
Alarmlist message No
Alarm evaluated All the time
Related applications AMF,MRS
Description
This alarm evaluates the Mains phase voltage in phases. The following setpoints
are related to it:
Mains Overvoltage (page 272)
Mains Overvoltage Delay (page 276)
Mains L1 Overvoltage
6 back to List of alarms level 2
Alarm Type MP
Alarmlist message No
Alarm evaluated All the time
Related applications AMF,MRS
Description
This alarm evaluates the Mains phase voltage in phases. The following setpoints
are related to it:
Mains Undervoltage (page 274)
Mains Undervoltage Delay (page 276)
Mains L1 Undervoltage