participating in the power management in particular control
group (this value is given for each gen-set as Nomin
current multiplied by GenNomV). Setpoints #LoadResStrt
X (e.g. LoadResStrt 1) and #LoadResStop X (e.g.
LoadResStop 1) are set in absolute values in kVA.
The power management is based on the relative load, i.e.
ratio active power to nominal power. Setpoints
#%LdResStrt X (e.g. %LdResStrt 1) and #%LdResStop X
(e.g. %LdResStop 1) are set in relative values in %.
Minimum allowable relative power reserve is evaluated
from nominal power of all running gen-sets combined in %.
NOTE:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
11.2.9.2 Setpoint: #PriorAutoSwap
DISABLED, RUN HOURS EQU, LD DEMAND SWAP [-]
This setpoint selects the method of optimalization of priorities
IM-NT does not provide the AutoSwap functions
for other controllers. Priorities in gen-set
controllers have their original values which do
not change.
Running Hours Equalization mode. All gen-sets
in the logical group are kept to work
approximately the same number of running
hours. See also setpoints RunHoursBase (e.g.
IGS-MINT application) and RunHrsMaxDiff. Up
to 32 engines can cooperate in this mode. For
more information on this function please refer to
running hours equalization.
For different sized engines, this mode allows to
optimally select the running engines according to
the actual site load. Up to 3 engines can
cooperate in this mode (if more gen-sets are
needed, please use IGS-NT-PSC firmware in
additional controller - more information about this