FW can be found on our webpages
www.comap.cz). Note that this priority swapping
function may be used only if #Pwr mgmt mode is
set to ABS (kW).
For different sized engines, this mode
automatically select optimum running gen-sets.
This function supports up to 32 gen-sets (or less
based on how many other controllers are used in
the installation). Not all combinations of gen-sets
are considered.
NOTE:
Setpoint Priority in gen-set controllers is not actually changed by AutoSwap
functions - the priority is changed only locally during AutoSwap function is
enabled. Note that after RHE is activated any changes in the actual priority
setpoints need to be confirmed by disabling and enabling RHE again to take
effect.
NOTE:
If the optimization is enabled at least one gen-set in the group must be set as
the master for the optimization (Priority ctrl = MASTER). It is possible to have
more than one master, the one with lowest CAN address will play the role of
the master and if it is switched off the next one will take the master role.
NOTE:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
CAUTION!
If the controller which is set to MASTER in PriorAutoSwap function is in
Emerg. manual, priority autoswapping will not work and no other controller
will assume MASTER role.