InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
368
Description
While this input is active the value of ExtValue 1 is contiously beeing
increased at the rate of ExtValue1 rate until it reaches ExtValue1HiLim.
NOTE:
If this input is used (configured), the ExtValue 1 can't be written remotely
from a remote terminal using the command ExtValue 1.
13.2.1.63 Binary input: ExtValue1 down
Related FW
standard v3.1.0
Description
While this input is active the value of ExtValue 1 is contiously beeing
decreased at the rate of ExtValue1 rate until it reaches ExtValue1LoLim.
NOTE:
If this input is used (configured), the ExtValue 1 can't be written remotely
from a remote terminal using the command ExtValue 1.
13.2.1.64 Binary input: ExtValue2 up
Related FW
standard v3.1.0
Description
While this input is active the value of ExtValue 2 is contiously beeing
increased at the rate of ExtValue2 rate until it reaches ExtValue2HiLim.
NOTE:
If this input is used (configured), the ExtValue 2 can't be written remotely
from a remote terminal using the command ExtValue 2.
13.2.1.65 Binary input: ExtValue2 down
Related FW
standard v3.1.0
Description
While this input is active the value of ExtValue 2 is contiously beeing
decreased at the rate of ExtValue2 rate until it reaches ExtValue2LoLim.
NOTE:
If this input is used (configured), the ExtValue 2 can't be written remotely
from a remote terminal using the command ExtValue 2.
13.2.1.66 Binary input: ExtValue3 up
Related FW
standard v3.1.0