11.2.12.24 Setpoint: ExtValue4HiLim
Group
Force value
Range [units]
ExtValue4LoLim .. 32000 [X]
Related FW
standard v3.1.0
Description
This setpoint adjusts the high limit of the value of ExtValue 4 if the value is
lowered/raised by the binary inputs ExtValue4 up and ExtValue4 down. The
ExtValue 4 is never raised over this limit.
NOTE:
This limit is not taken into account if the value ExtValue 4 is written remotely
from a terminal using the appropriate command ExtValue #n.
11.2.12.25 Setpoint: ExtValue1 rate
Group
Force value
Range [units]
1 .. 10000 [X/s]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint adjusts the rate pre second at which the ExtValue 1 is beeing
changed while the input ExtValue1 up or ExtValue1 down is active.
11.2.12.26 Setpoint: ExtValue2 rate
Group
Force value
Range [units]
1 .. 10000 [X/s]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint adjusts the rate pre second at which the ExtValue 2 is beeing
changed while the input ExtValue2 up or ExtValue2 down is active.
11.2.12.27 Setpoint: ExtValue3 rate
Group
Force value