EasyManua.ls Logo

ComAp InteliMains NT IM-NT-BB - Page 390

ComAp InteliMains NT IM-NT-BB
437 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
390
If more then one binary input for MinRunPower is activated, the one with the
highest number is used (i.e. its corresponding value).
CAUTION!
All controllers cooperating together in Power management must have the
same minimal running power selected.
NOTE:
It is possible to use virtual peripheries for distribution of the binary signal from
one physical switch connected to one controller to all other controllers over
the CAN bus. See the principial diagram of such distribution in the description
of the input Load res 2.
13.2.1.106 Binary input: MinRun power 3
Related FW
standard v3.1.0
Description
This input is used to activate the function Minimal running power #3, which is
adjusted by setpoint #MinRunPower 3.
NOTE:
The default value of minimal running power, which takes place while none of
the inputs MinRun power x, is 0kW.
NOTE:
If more then one binary input for MinRunPower is activated, the one with the
highest number is used (i.e. its corresponding value).
CAUTION!
All controllers cooperating together in Power management must have the
same minimal running power selected.
NOTE:
It is possible to use virtual peripheries for distribution of the binary signal from
one physical switch connected to one controller to all other controllers over
the CAN bus. See the principial diagram of such distribution in the description
of the input Load res 2.
13.2.1.107 Binary input: MCBIsolated
Related FW
standard v3.1.0
Description
This input can be used for secondary breaker feedback. When this logical
binary input gets activated the controller will consider the corresponding CB

Table of Contents