The reaction on changes of these inputs is delayed about 1 sec to ensure the
new combination is valid (e.g. if a rotary selector switch is used).
CAUTION!
Each language change causes the reinitialization of the display. Function of
the controller is not influenced.
13.2.1.104 Binary input: MinRun power 1
This input is used to activate the function Minimal running power #1, which is
adjusted by setpoint #MinRunPower 1.
NOTE:
The default value of minimal running power, which takes place while none of
the inputs MinRun power x, is 0kW.
NOTE:
If more then one binary input for MinRunPower is activated, the one with the
highest number is used (i.e. its corresponding value).
CAUTION!
All controllers cooperating together in Power management must have the
same minimal running power selected.
NOTE:
It is possible to use virtual peripheries for distribution of the binary signal from
one physical switch connected to one controller to all other controllers over
the CAN bus. See the principial diagram of such distribution in the description
of the input Load res 2.
13.2.1.105 Binary input: MinRun power 2
This input is used to activate the function Minimal running power #2, which is
adjusted by setpoint #MinRunPower 2.
NOTE:
The default value of minimal running power, which takes place while none of
the inputs MinRun power x, is 0kW.
NOTE: