InteliNano-NT Plus, SW version 2.0.1.x, ©ComAp July 2015
39
O03
Stop Solenoid
This output is dedicated to control the stop solenoid (valve). The output closes when an engine stop
command is received and remains active until the gen-set is stopped.
The engine is stopped if:
RPM < 2
and
Generator voltage < 10V
and
Oil pressure < 3 Bar. (43 PSI)
Fuel Solenoid is
opened
Gen-set stoped
On
Off
Time
Stop
Engine run
10 s
Oil Pressure
Stop Solenoid
Output
Generator voltage
Cooling Time
D+
RPM / Frequency
Stop Time 60 s
Fuel Solenoid
is opened
Gen-set stoped
On
Off
Time
Stop
Engine run
10 s
Oil Pressure
Stop Solenoid
Output
Generator voltage
Cooling Time
D+
RPM / Frequency
Stop Time 60 s
Stop Fail Warning