InteliNano-NT Plus, SW version 2.0.1.x, ©ComAp – July 2015
73
A – AMF (Auto Mains Failure) settings 10.4
Delay between the mains failure and the automatic start of the gen-set to an AMF operation.
This is a "mains stabilization" time. Timer begins when mains returns. If the mains are continuously
healthy for this period, the controller will finish the AMF operation.
1 % of nominal system voltage
A04 Mains Undervoltage – 150%
Threshold for detection of mains failure due to overvoltage. The setpoint is adjusted relative to the
nominal system voltage (setpoint B01 Nominal Voltage Ph-N or B02 Nominal Voltage Ph-Ph
depending on B04 Connection Type setting).
1 % of nominal system voltage
50 – A03 Mains Overvoltage
Threshold for detection of mains failure due to overvoltage. The setpoint is adjusted relative to the
nominal system voltage (setpoint B01 Nominal Voltage Ph-N or B02 Nominal Voltage Ph-Ph
depending on B04 Connection Type setting).