ComAp InteliNano NT Plus - A - AMF (Auto Mains Failure) Settings

ComAp InteliNano NT Plus
90 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliNano-NT Plus, SW version 2.0.1.x, ©ComAp July 2015
73
A AMF (Auto Mains Failure) settings 10.4
A01
Emergency Start Delay
Units:
seconds [s]
Step:
1 s
Range:
0 600 s
Default value:
5
Delay between the mains failure and the automatic start of the gen-set to an AMF operation.
A02
Mains Return Delay
Units:
seconds [s]
Step:
1 s
Range:
1 3600 s
Default value:
20 s
This is a "mains stabilization" time. Timer begins when mains returns. If the mains are continuously
healthy for this period, the controller will finish the AMF operation.
A03
Mains Overvoltage
Units:
percentage [%]
Step:
1 % of nominal system voltage
Range:
A04 Mains Undervoltage 150%
Default value:
110 %
Delay:
0,1 s
Threshold for detection of mains failure due to overvoltage. The setpoint is adjusted relative to the
nominal system voltage (setpoint B01 Nominal Voltage Ph-N or B02 Nominal Voltage Ph-Ph
depending on B04 Connection Type setting).
A04
Mains Undervoltage
Units:
percentage [%]
Step:
1 % of nominal system voltage
Range:
50 A03 Mains Overvoltage
Default value:
60 %
Delay:
0,1 s
Threshold for detection of mains failure due to overvoltage. The setpoint is adjusted relative to the
nominal system voltage (setpoint B01 Nominal Voltage Ph-N or B02 Nominal Voltage Ph-Ph
depending on B04 Connection Type setting).