Mains Overfrequency
Units:
percentage [%]
Step:
1 %
Range:
A06 Mains Underfrequency 150 %
Default value:
102 %
Delay:
0,1 s
Threshold for detection of mains failure due to overfrequency. The setpoint is adjusted relative to the
system nominal frequency (setpoint B03 Nominal Frequency).
A06
Mains Underfrequency
Units:
percentage [%]
Step:
1 %
Range:
50 A05 Mains Overfrequency %
Default value:
98 %
Delay:
0,1 s
Threshold for detection of mains failure due to underfrequency. The setpoint is adjusted relative to the
system nominal frequency (setpoint B03 Nominal Frequency).