InteliNano-NT Plus, SW version 2.0.1.x, ©ComAp July 2015
67
E - Engine parameters and protections 10.2
E01
Prestart Time
Units:
seconds [s]
Step:
1s
Range:
0-600s
Default value:
2
Time of closing of the O08 Prestart output prior to the engine start.
Set to zero if you want to leave the output O08 Prestart open.
E02
Maximum Cranking Time
Units:
seconds [s]
Step:
1s
Range:
0-60s
Default value:
5
Maximum duration when the starter motor is energized.
E03
Cooling Time
Units:
seconds [s]
Step:
1s
Range:
0-3600s
Default value:
30
Runtime of the unloaded gen-set to cool the engine before stop.
E04
Oil Pressure Shutdown
Units:
Bar [Bar]
Step:
0,1 Bar
Range:
0-10 Bar
Default value:
1 Bar
Delay:
3 s
Shutdown threshold level for I23 Oil Pressure Analog input.
E05
Coolant Temperature Shutdown
Units:
degree Celsius [°C]
Step:
1 °C
Range:
0 -150 °C
Default value:
90 °C
Delay:
5 s
Shutdown threshold level for I25 Coolant Temperature Analog input.