InteliNano-NT Plus, SW version 2.0.1.x, ©ComAp July 2015
66
B09
Nominal Current
Units:
Ampere [A]
Step:
1 A
Range:
1 1000 A
Default value:
50 A
It is nominal generator current. This value is used as a base for Generator Short Circuit alarm
(shutdown). For overcurrent limit set the setpoint Generator Short Circuit Shutdown.
Nominal Current can be different from generator rated current value.
B10
CT Ratio
Units:
Ampere [A]
Step:
A / 5 A
Range:
1 5000 A
Default value:
50 A
Gen-set phases current transformers ratio.
For CT Ratio < 50 the values of power and current are displayed in a controller with one decimal.
For CT Ratio 50 the values of power and current are displayed in a controller with integral numbers.
B11
Nominal RPM
Units:
RPM
Step:
1
Range:
100-4000
Default value:
1500
Nominal engine speed.