InteliNano-NT Plus, SW version 2.0.1.x, ©ComAp – July 2015
65
The controller is switched to Zero Power Mode when there is no user interaction with the controller for
the preset time. Zero Power Mode is disabled in AMF mode. Value 0 also disables this function. For
the controller wake up press button Start or activate input T11. The controller will not switch to Zero
Power Mode if any alarm is active.
This setpoint is available only when B06 AMF Function is disabled. When this setpoint is enabled,
the controller is switched to special operation mode. First screen was changed and generator voltage
measurement is hides in this operation mode.
First main screen shows battery voltage, running hours and engine status (stop,
starting/stopping, run) via symbol in light tower reflector (upper left corner).
Second screen shows all analog values which are available. (Oil Pressure, Coolant
Temperature; Fuel Level and Battery Voltage)
Last screen is event log.
Figure 10.4
LIGHTTOWER SCREENS