EasyManua.ls Logo

ComAp InteliNano NT Plus

ComAp InteliNano NT Plus
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliNano-NT Plus, SW version 2.0.1.x, ©ComAp July 2015
65
B07
Zero Power Mode Delay
Units:
minutes [min]
Step:
1 minute
Range:
0-360 minutes
Default value:
0
The controller is switched to Zero Power Mode when there is no user interaction with the controller for
the preset time. Zero Power Mode is disabled in AMF mode. Value 0 also disables this function. For
the controller wake up press button Start or activate input T11. The controller will not switch to Zero
Power Mode if any alarm is active.
B08
Light Tower Mode
Units:
Step:
Range:
1,2
Default value:
1
This setpoint is available only when B06 AMF Function is disabled. When this setpoint is enabled,
the controller is switched to special operation mode. First screen was changed and generator voltage
measurement is hides in this operation mode.
Setpoint code
Value
Meaning
E08
1
Disable
E08
2
Enable
First main screen shows battery voltage, running hours and engine status (stop,
starting/stopping, run) via symbol in light tower reflector (upper left corner).
Second screen shows all analog values which are available. (Oil Pressure, Coolant
Temperature; Fuel Level and Battery Voltage)
Last screen is event log.
Figure 10.4
LIGHTTOWER SCREENS

Other manuals for ComAp InteliNano NT Plus

Related product manuals