InteliNano-NT Plus, SW version 2.0.1.x, ©ComAp July 2015
68
E15
Fuel Level Shutdown
Units:
%
Step:
1
Range:
0 - 20
Default value:
10
When this protection is activated the red LED above Stop button will blink, the general shutdown
symbol will be displayed on LCD’s upper right corner. Fuel Level SD symbol will be displayed on event
log with running hours stamp and the shutdown procedure will occur.
Input has 10s delay.
E06
Battery Undervoltage
Units:
Volts [V]
Step:
0,1 V
Range:
8 40 V
Default value:
11,5 V
Delay:
30 s
Warning threshold for Low Battery voltage.
E07
Warning Maintenance
Units:
hours [h]
Step:
1 h
Range:
0 10000 h
Default value:
9999 h
Counts down when the engine is running. When the counter reaches zero, an alarm will appear.
When the value 10000 is set, than the Maintenance function is disabled and counter will not count.
Counter value will not appear in the controller’s statistics. Maximum value for running countdown is
9999. Warning Maintenance will appear when counter time has elapsed.
E08
Oil Pressure Starter Disengagement
Units:
Step:
Range:
1,2
Default value:
1
When this setpoint is enabled, the controller will use Low Oil Pressure or Oil Pressure Analog
signal for starter disengagement. Starter will disengaged when oil pressure reach starting oil pressure
or binary input Low Oil Pressure will be opened (Normally Open contact) or closed (Normally
Close contact).
When is disabled then only RPM (frequency), generator voltage or D+ will be used for starter
disengagement.
Setpoint code
Value
Meaning
E08
1
Disable
E08
2
Enable