InteliNano-NT Plus, SW version 2.0.1.x, ©ComAp July 2015
70
E10
Minimal Stabilization Time
Units:
seconds [s]
Step:
1 s
Range:
1 300 s
Default value:
3 s
Delay:
Minimum time after reaching of defined level of RPM to the closing GCB.
Prestart Time
> 8 s
Maximum
Cranking Time
0 - 60 s
Gen-set start failed shutdown,
if the voltage or frequency are not in
the limit
On
Off
TimeStart
Engine run
Max. Stab. Time 7 sMin. Stab. Time
Gen-set can be
loaded
Starter Output
Gen-set can be loaded
only when all running
condition are satisfied
E11
Starting RPM
Units:
%
Step:
1
Range:
5 60
Default value:
25
When Starting RPM are reached controller stops cranking. (Starter is disengaged.)