InteliNano-NT Plus, SW version 2.0.1.x, ©ComAp July 2015
84
External Shutdown 3
GCB Fail
Failure of generator circuit breaker.
Generator Overvoltage
Generator will stop when output voltage exceeds the preset threshold G01 Generator
Overvoltage Shutdown.
Generator Undervoltage
Generator will stop when output voltage drops below the preset threshold G02
Generator Undervoltage Shutdown.
Generator Overfrequency
The generator frequency is out of limits given by setpointsG03 Generator
Overfrequency Shutdown and G04 Generator Underfrequency Shutdown .
Generator Underfrequency
The generator frequency is out of limits given by setpointsG03 Generator
Overfrequency Shutdown and G04 Generator Underfrequency Shutdown .
Generator CCW Rotation
Incorrect generator phase sequence.
Start Fail
Gen-set start failed.
Stop Fail
Gen-set stop failed.
Battery Flat
If the controller loses power during starting sequence due to bad battery condition, it
will not try to start again and will activate this protection.