46
power limit [%]
100
Flushing cycle
Thefollowingindicationsareprovidedforthesetushinginterval:
Left: Switchsettingonrotaryswitch“S1”
Right: Setushinginterval
Note:Theushingintervalissetonswitch“S1”onthecontrolboard.Please
observe the notes in chapter 6.1.
Stand-by heating
Stand-by heating activated (“on”)/deactivated(“off”).
Note:Ifstand-byheatingisactivethewatertemperatureinthesteamcylinder
isconstantlykeptatapprox.70°C.Stand-byheatingmaybeactivated/deac-
tivatedwiththeDIPswitch“S4-1”onthecontrolboard.Pleaseobservethe
information given in chapter 6.1.
Capacity limitation
Thesetcapacitylimitationasapercentageofthemaximumcapacity.
Soft start
Softstartenabled(“on”)/disabled(“off”).
Note:Afterrestartoraftertheunithasbeenidlefor4hours(stand-by)theSoft
startfunctionreducesthehumidicationcapacitytoapresetvalueforaselect-
ableperiod(valuesettingsseeparametersbelow).
Time limit for Soft start
Selected time limit for Soft start function in minutes.
Note: This menu item is available only if the Soft start function is enabled.
Capacity limit for Soft start
SelectedcapacitylimitforSoftstartfunctionin%ofmaximumcapacity.
Note: This menu item is available only if the Soft start function is enabled.
Demineralization mode
Demineralizationmodeenabled(“on”)/disabled(“off”).
Note:TheDemineralizationmodeushesthesteamcylinderwithinanhour
afterapresetnumberofscumdetectionshastakenplace(seeDemineraliza-
tiondelay).Thispreventstheformationofscum.
Demineralization delay
Selectedthedelayfordemineralization.
Note: This menu item is available only if the Demineralization mode is
enabled.
Note:Thisvaluedeterminesthenumberofscumdetectionsallowed(maxi-
mumlevelinsteamcylinderisreached)beforethesteamcylinderisushed
for a preset time.
stand-by heating
on
drain cycle
4: 120
softstart
on
softstart time
30 Min
softst. power
50 %
demineral. mode
on
demineral. delay
3