11.2.7.1
Control Structure in VVC
+
+
_
+
_
Cong. mode
Ref.
Process
P 1-00
High
+f max.
Low
-f max.
P 4-11
Motor speed
low limit (RPM)
P 4-12
Motor speed
low limit (Hz)
P 4-13
Motor speed
high limit (RPM)
P 4-14
Motor speed
high limit (Hz)
Motor
controller
Ramp
Speed
PID
P 7-20 Process feedback
1 source
P 7-22 Process feedback
2 source
P 7-00 Speed PID
feedback source
P 1-00
Cong. mode
P 4-19
Max. output freq.
-f max.
Motor
controller
P 4-19
Max. output freq.
+f max.
P 3-**
P 7-0*
130BA055.10
Figure 11.8 Control Structure in VVC
+
Open Loop and Closed-loop Congurations
In Figure 11.8, the resulting reference from the reference handling system is received and fed through the ramp limitation
and speed limitation before being sent to the motor control. The output of the motor control is then limited by the
maximum frequency limit.
Parameter 1-01 Motor Control Principle is set to [1] VVC
+
and parameter 1-00 Conguration Mode is set to [0] Speed open loop.
If parameter 1-00 Conguration Mode is set to [1] Speed closed loop, the resulting reference is passed from the ramp
limitation and speed limitation into a speed PID control. The speed PID control parameters are located in parameter group
7-0* Speed PID Ctrl. The resulting reference from the speed PID control is sent to the motor control limited by the frequency
limit.
Select [3] Process in parameter 1-00 Conguration Mode to use the process PID control for closed-loop control of, for example,
speed or pressure in the controlled application. The process PID parameters are in parameter groups 7-2* Process Ctrl. Feedb
and 7-3* Process PID Ctrl.
Basic Operating Principles ... Design Guide
MG22B222 Danfoss A/S © 01/2018 All rights reserved. 195