[9] Active Set-up Update parameters in set-up selected as
Active Set-up
(see par.
0-10).
0-12 Link Set-ups
Option: Function:
The link ensures synchronizing of the “not changeable during
operation” parameter values enabling shift from one set-up to
another during operation.
If the set-ups are not linked, a change between them is not
possible while the motor is running. Thus the set-up change
does not occur until the motor is coasted.
[0] Not linked Leaves parameters unchanged in both set-ups and cannot be
changed while motor runs.
[1 ]
*
Linked Copy parameters “not changeable during operation” parameter
values into presently selected
Edit Set-up
.
NB!
This parameter cannot be changed while motor
runs.
4.1.2. 0-4* LCP Keypad
The frequency converter can operate in the following three modes:
Hand
,
Off
and
Auto
.
Hand:
The frequency converter is locally operated and does not allow any remote control. By
activating Hand a start signal is given.
OFF:
The frequency converter stops with a normal stop ramp. When Off is chosen the frequency
converter can only be started by pressing either Hand or Auto on the LCP.
Auto:
In Auto-mode the frequency converter can be remote controlled (bus/digital).
0-40 [Hand on] Key on LCP
Option: Function:
[0] Disabled Hand-on key has no function.
[1 ]
*
Enabled Hand-on key is functional.
0-41 [Off/Reset] Key on LCP
Option: Function:
[0] Disable Off/Reset Off/reset key has no function.
[1 ]
*
Enable Off/Reset Stop signal and reset of any faults.
[2] Enable Reset Only Reset only. Stop (Off) function is disabled.
0-42 [Auto on] Key on LCP
Option: Function:
[0] Disabled Auto-on key has no function.
[1 ]
*
Enabled Auto-on key is functional.