4.11.4. Trip Reset, 14-2*
Parameters for configuring auto reset handling, special trip handling and control card self test or
initialisation.
14-20 Reset Mode
Option: Function:
Select reset function after tripping. Once reset, frequency con-
verter can be restarted.
[0]
*
Manual Reset Perform reset via [reset]-button or digital inputs.
[1] AutoReset 1 Performs one automatic reset after tripping.
[2] AutoReset 2 Performs two automatic resets after tripping.
[3] AutoReset 3 Performs three automatic resets after tripping.
[4] AutoReset 4 Performs four automatic resets after tripping.
[5] AutoReset 5 Performs five automatic resets after tripping.
[6] AutoReset 6 Performs six automatic resets after tripping.
[7] AutoReset 7 Performs seven automatic resets after tripping.
[8] AutoReset 8 Performs eight automatic resets after tripping.
[9] AutoReset 9 Performs nine automatic resets after tripping.
[10] AutoReset 10 Performs ten automatic resets after tripping.
[11] AutoReset 15 Performs fifteen automatic resets after tripping.
[12] AutoReset 20 Performs twenty automatic resets after tripping.
[13] Infinite auto reset Performs an infinite number of automatic resets after tripping.
Motor may start without warning.
14-21 Automatic Restart Time
Range: Function:
10 s
*
[0 - 600 s] Enter time interval from trip to start of automatic reset function.
This parameter is active when par. 14-20,
Reset Mode
, is set to
Automatic Reset
[0] - [13].
4. Parameter Descriptions VLT Micro Drive FC 51
66
MG.02.C2.02 - VLT
®