The value must be set to min. 2 mA in order to activate the Live Zero Timeout
function in par. 6-01.
6-23 Terminal 60 High Current
Range: Function:
This reference signal should correspond to the high current val-
ue set in par. 6-25.
20.00
mA
*
[0.10 - 20.00 mA] Enter high current value.
6-24 Terminal 60 Low Ref./Feedb. Value
Range: Function:
The scaling value should correspond to the minimum reference
feedback value set in par. 3-02.
0.000
*
[-4999 - 4999] Enter analog input scaling value.
6-25 Terminal 60 High Ref./Feedb. Value
Range: Function:
The scaling value should correspond to the maximum reference
feedback value set in par. 3-03.
50.00
*
[-4999 - 4999] Enter analog input scaling value.
6-26 Terminal 54 Filter Time Constant
Range: Function:
A first-order digital low pass filter time constant for suppressing
electrical noise in terminal 54. A high time constant value im-
proves dampening, but also increases time delay through the
filter.
NB!
This parameter cannot be changed while motor
runs.
0.001 s
*
[0.001 - 10.00 s] Enter time constant.
4.7.5. 6-8* LCP Potmeter
The LCP potmeter can be selected either as Reference Resource or Relative Reference Resource.
NB!
In Hand mode the LCP potmeter functions as local reference.
VLT Micro Drive FC 51 4. Parameter Descriptions
MG.02.C2.02 - VLT
®
is a registered Danfoss trademark
47
4