[1] Bus Activation via serial communication port.
[2] LogicAnd Activation via serial communication port and a digital input.
[3]
*
LogicOr Activation via serial communication port or a digital input.
4.9.6. 8-9* Bus Feedback
Parameter for configuring bus feedback.
8-94 Bus Feedback 1
Range: Function:
0
*
[0x8000 - 0x7FFF] Bus feedback is delivered via FC or Modbus by writing the feed-
back value into this parameter.
4. Parameter Descriptions VLT Micro Drive FC 51
56
MG.02.C2.02 - VLT
®
is a registered Danfoss trademark