8-33 FC Port Parity
Option: Function:
This parameter only affects Modbus as FC bus always has even
parity.
[0]
*
No Parity
[1] Odd parity
[2] No Parity (2 stopbit)
[3] No Parity (1 stopbit)
8-35 Minimum Response Delay
Range: Function:
10 ms [1 - 500 ms] Specify minimum delay time between receiving a request and
transmitting a response.
8-36 Max Response Delay
Range: Function:
5.000 s
*
[0.010 - 10.00 s] Specify maximum permissible delay time between transmitting
a request and receiving a response. Exceeding this time delay
causes control word timeout.
4.9.5. 8-5* Digital/Bus
Parameters for configuring control word Digital/Bus merging.
NB!
Parameters are only active when par. 8-01,
Control SIte
, is set to
Digital and control
word
[0].
8-50 Coasting Select
Option: Function:
Select control of coasting function via digital input and/or bus.
[0] Digital Input Activation via a digital input.
[1] Bus Activation via serial communication port.
[2] LogicAnd Activation via serial communication port and a digital input.
[3]
*
LogicOr Activation via serial communication port or a digital input.
8-51 Quick Stop Select
Option: Function:
Select control of quick stop function via digital input and/or bus.
[0] Digital Input Activation via a digital input.
[1] Bus Activation via serial communication port.
[2] LogicAnd Activation via serial communication port and a digital input.