13-52 SL Controller Action
Array [20]
Select action corresponding to SLC event. Actions are executed
when corresponding event (par. 13-51) is evaluated as
True
.
[0]
*
Disabled Function is disabled.
[1] No Action No action is taken.
[2] Select Set-up1 Changes active set-up to Set-up 1.
[3] Select Set-up2 Changes active set-up to Set-up 2.
[10] SelectPresetRef0 Selects preset reference 0
[11] SelectPresetRef1 Selects preset reference 1
[12] SelectPresetRef2 Selects preset reference 2
[13] SelectPresetRef3 Selects preset reference 3
[14] SelectPresetRef4 Selects preset reference 4
[15] SelectPresetRef5 Selects preset reference 5
[16] SelectPresetRef6 Selects preset reference 6
[17] SelectPresetRef7 Selects preset reference 7
[18] SelectRamp1 Selects ramp 1
[19] SelectRamp2 Selects ramp 2
[22] Run Issues start command to frequency converter.
[23] RunReverse Issues start reverse command to frequency converter.
[24] Stop Issues stop command to frequency converter.
[25] Qstop Issues quick stop command to frequency converter.
[26] DCstop Issues DC stop command to frequency converter.
[27] Coast Frequency converter coasts immediately. All stop commands in-
cluding coast command stop the SLC.
[28] Freeze Output Freezes output frequency.
[29] StartTimer0 Starts timer 0.
[30] StartTimer1 Starts timer 1
[31] StartTimer2 Starts timer 2
[32] SetDO42Low Digital output 42 is low.
[33] SetRelayLow Relay is low.
[38] SetDO42High Digital output 42 is high.
[39] SetRelayHigh Relay is high.
[60] ResetCounterA Resets counter A to 0.
[61] ResetCounterB Resets counter B to 0.
4. Parameter Descriptions VLT Micro Drive FC 51