[7] Select Set-up 1 Change to Set-up 1 upon reestablishment of communication
following a control word timeout.
[8] Select Set-up 2 Change to Set-up 2 upon reestablishment of communication
following a control word timeout.
8-06 Reset Control Word Timeout
Option: Function:
Resetting the control word timeout will remove any timeout
function.
[0]
*
No Function Control word timeout is not reset.
[1] Do Reset Control word timeout is reset, and parameter goes into
No
Function
state.
4.9.3. 8-3* FC Port Settings
Parameters for configuring the FC Port.
4.9.4. 8-30 Protocol
8-30 Protocol
Option: Function:
Select the protocol to be used. Note that changing protocol will
not be effective until after powering off the frequency converter.
[0]
*
FC
[2] Modbus
8-31 Address
Range: Function:
Select the address for the bus.
1
*
[1 - 126] FC -bus range is 1-126.
Modbus range is 1-247.
8-32 FC Port Baud Rate
Option: Function:
Select baud rate for FC Port.
NB!
Changing baud rate will be effective after re-
sponding to any ongoing bus-requests.
[0] 2400 Baud
[1] 4800 Baud
[2]
*
9600 Baud
VLT Micro Drive FC 51 4. Parameter Descriptions
MG.02.C2.02 - VLT
®
is a registered Danfoss trademark
53