[7] Select Set-up 1 Change to Set-up 1 upon reestablishment of communication
following a control word timeout.
[8] Select Set-up 2 Change to Set-up 2 upon reestablishment of communication
following a control word timeout.
8-06 Reset Control Word Timeout
Option: Function:
Resetting the control word timeout will remove any timeout
function.
[0]
*
No Function Control word timeout is not reset.
[1] Do Reset Control word timeout is reset, and parameter goes into
No
Function
state.
4.9.3. 8-3* FC Port Settings
Parameters for configuring the FC Port.
4.9.4. 8-30 Protocol
8-30 Protocol
Option: Function:
Select the protocol to be used. Note that changing protocol will
not be effective until after powering off the frequency converter.
[0]
*
FC
[2] Modbus
8-31 Address
Range: Function:
Select the address for the bus.
1
*
[1 - 126] FC -bus range is 1-126.
Modbus range is 1-247.
8-32 FC Port Baud Rate
Option: Function:
Select baud rate for FC Port.
NB!
Changing baud rate will be effective after re-
sponding to any ongoing bus-requests.
[0] 2400 Baud
[1] 4800 Baud
[2]
*
9600 Baud
VLT Micro Drive FC 51 4. Parameter Descriptions
MG.02.C2.02 - VLT
®
is a registered Danfoss trademark
53
4

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 51 Series and is the answer not in the manual?

Danfoss VLT FC 51 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 51 Series
CategoryDC Drives
LanguageEnglish

Related product manuals