EasyManuals Logo

Danfoss VLT FC 51 Series User Manual

Danfoss VLT FC 51 Series
83 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #32 background imageLoading...
Page #32 background image
3-14 Preset Relative Reference
Range: Function:
0.00% [-100.00 - 100.00%] Define fixed value in % to be added to variable value defined in
par. 3-18,
Relative Scaling Reference Source
.
The sum of fixed and variable values (labelled Y in illustration
below) is multiplied with actual reference (labelled X in illusta-
tion). This product is added to actual reference
X
+
X
×
Y
100
3-15 Reference 1 Source
Option: Function:
Par. 3-15, 3-16 and 3-17 define up to three different reference
signals. The sum of these reference signals defines the actual
reference.
[0] No Function No reference signal is defined.
[1]
*
Analog Input 53 Use signals from analog input 53 as reference, see par. 6-1*.
[2] Analog Input 60 Use signals from analog input 60 as reference, see par. 6-2*.
[11] Local Bus Ref. Use signals from local bus as reference, see par. 8-9*.
[21] LCP Potentiometer Use signals from LCP potentiometer as reference, see par. 6-8*.
[8] Pulse input Use signals from pulse input as reference, see par. 5-5*.
3-16 Reference 2 Source
Option: Function:
See Par. 3-15 for description.
[0] No Function No reference signal is defined.
[1] Analog Input 53 Use signals from analog input 53 as reference.
[2]
*
Analog Input 60 Use signals from analog input 60 as reference.
[11] Local Bus Ref. Use signals from local bus as reference.
[21] LCP Potentiometer Use signals from LCP potentiometer as reference.
3-17 Reference 3 Source
Option: Function:
See Par. 3-15 for description.
[0] No Function No reference signal is defined.
[1] Analog Input 53 Use signals from analog input 53 as reference.
4. Parameter Descriptions VLT Micro Drive FC 51
32
MG.02.C2.02 - VLT
®
is a registered Danfoss trademark
4

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 51 Series and is the answer not in the manual?

Danfoss VLT FC 51 Series Specifications

General IconGeneral
EnclosureIP20
Operating Temperature-10°C to +40°C (without derating), up to +50°C (with derating)
Output Voltage0 to input voltage
Protection FeaturesOvercurrent, overvoltage, undervoltage, short circuit, overload, overtemperature, ground fault
Cooling MethodForced convection
Input Voltage200-240V AC, 380-480V AC

Related product manuals