4.1.3. 0-5* Copy/Save
0-50  LCP Copy
Option: Function:
The detachable LCP of the frequency converter can be used for
storing setups, and thus for transferring data when moving pa-
rameter settings from one frequency converter to another.
NB!
LCP Copy
 can only be activated from the LCP and
ONLY when the motor is coasted.
[1] All to LCP Copy all setups from the frequency converter into the LCP.
[2] All from LCP Copy all setups from LCP to frequency converter.
[3] Size indep. from LCP Copy non motor size dependent data from LCP to frequency
converter
0-51  Set-up Copy
Option: Function:
Use this function to copy a set-up content into the 
Edit Set-up
.
In order to be able to make a set-up copy ensure that
•the motor is coasted
• par. 0-10, 
Active Set-up
, is set to either 
Set-up 1
 [1]
or 
Set-up 2
 [2]
NB!
The keyboard/parameter database are blocked
while Set-up Copy is running.
[0 ] 
*
No Copy Copy function is inactive
[1] Copy from Set-up 1 Copy from 
Set-up 1
 to edit set-up chosen in par. 0-11, 
Edit Set-
up
.
[2] Copy from Set-up 2 Copy from 
Set-up 2
 to edit set-up chosen in par. 0-11, 
Edit Set-
up
.
[9] Copy from Factory
Set-up
Copy from Factory Settings to edit set-up chosen in par. 0-11,
Edit set-up
.
4.1.4. 0-6* Password
0-60  (Main) Menu Password
Range: Function:
Use password for protection against unintended change of sen-
sitive parameters, eg. motor parameters.
Password protected parameters can always be read, but cannot
be edited without entering the password.
4. Parameter Descriptions VLT Micro Drive FC 51
16
 MG.02.C2.02 - VLT
®
 is a registered Danfoss trademark   
4