4.1.3. 0-5* Copy/Save
0-50 LCP Copy
Option: Function:
The detachable LCP of the frequency converter can be used for
storing setups, and thus for transferring data when moving pa-
rameter settings from one frequency converter to another.
NB!
LCP Copy
can only be activated from the LCP and
ONLY when the motor is coasted.
[1] All to LCP Copy all setups from the frequency converter into the LCP.
[2] All from LCP Copy all setups from LCP to frequency converter.
[3] Size indep. from LCP Copy non motor size dependent data from LCP to frequency
converter
0-51 Set-up Copy
Option: Function:
Use this function to copy a set-up content into the
Edit Set-up
.
In order to be able to make a set-up copy ensure that
•the motor is coasted
par. 0-10,
Active Set-up
, is set to either
Set-up 1
[1]
or
Set-up 2
[2]
NB!
The keyboard/parameter database are blocked
while Set-up Copy is running.
[0 ]
*
No Copy Copy function is inactive
[1] Copy from Set-up 1 Copy from
Set-up 1
to edit set-up chosen in par. 0-11,
Edit Set-
up
.
[2] Copy from Set-up 2 Copy from
Set-up 2
to edit set-up chosen in par. 0-11,
Edit Set-
up
.
[9] Copy from Factory
Set-up
Copy from Factory Settings to edit set-up chosen in par. 0-11,
Edit set-up
.
4.1.4. 0-6* Password
0-60 (Main) Menu Password
Range: Function:
Use password for protection against unintended change of sen-
sitive parameters, eg. motor parameters.
Password protected parameters can always be read, but cannot
be edited without entering the password.
4. Parameter Descriptions VLT Micro Drive FC 51
16
MG.02.C2.02 - VLT
®
is a registered Danfoss trademark
4

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 51 Series and is the answer not in the manual?

Danfoss VLT FC 51 Series Specifications

General IconGeneral
EnclosureIP20
Operating Temperature-10°C to +40°C (without derating), up to +50°C (with derating)
Output Voltage0 to input voltage
Protection FeaturesOvercurrent, overvoltage, undervoltage, short circuit, overload, overtemperature, ground fault
Cooling MethodForced convection
Input Voltage200-240V AC, 380-480V AC