8 General Specifications and Troubleshooting
8.1 Line Power Supply Specifications
8.1.1 Line Power Supply 3x200–240 V AC
Adjustable
frequency drive
PK25 PK37 PK75 P1K5 P2K2 P3K7 P5K5 P7K5 P11K P15K P18K P22K P30K P37K P45K
Typical shaft output
[kW]
0.25 0.37 0.75 1.5 2.2 3.7 5.5 7.5 11.0 15.0 18.5 22.0 30.0 37.0 45.0
Typical shaft output
[hp]
0.33 0.5 1.0 2.0 3.0 5.0 7.5 10.0 15.0 20.0 25.0 30.0 40.0 50.0 60.0
IP20 frame H1 H1 H1 H1 H2 H3 H4 H4 H5 H6 H6 H7 H7 H8 H8
Max. cable size in
terminals (line
power, motor)
[mm
2
/AWG]
4/10 4/10 4/10 4/10 4/10 4/10 16/6 16/6 16/6 35/2 35/2 50/1 50/1 95/0 120/
(4/0)
Output current
104 °F [40 °C] ambient temperature
Continuous
(3x200–240 V) [A]
1.5 2.2 4.2 6.8 9.6 15.2 22.0 28.0 42.0 59.4 74.8 88.0 115.0 143.0 170.0
Intermittent
(3x200–240 V) [A]
1.7 2.4 4.6 7.5 10.6 16.7 24.2 30.8 46.2 65.3 82.3 96.8 126.5 157.3 187.0
Max. input current
Continuous
3x200–240 V) [A]
1.1 1.6 2.8 5.6 8.6/
7.2
14.1/
12.0
21.0/
18.0
28.3/
24.0
41.0/
38.2
52.7 65.0 76.0 103.7 127.9 153.0
Intermittent
(3x200–240 V) [A]
1.2 1.8 3.1 6.2 9.5/
7.9
15.5/
13.2
23.1/
19.8
31.1/
26.4
45.1/
42.0
58.0 71.5 83.7 114.1 140.7 168.3
Max. electrical fuses
See chapter 5.2.3 Fuses and Circuit Breakers
Estimated power loss
[W], Best case/
typical
1)
12/
14
15/
18
21/
26
48/
60
80/
102
97/
120
182/
204
229/
268
369/
386
512 697 879 1149 1390 1500
Weight enclosure
IP20 lb [kg]
4.41
[2.0]
4.41
[2.0]
4.41
[2.0]
4.63
[2.1]
7.5
[3.4]
9.92
[4.5]
17.42
[7.9]
17.42
[7.9]
20.94
[9.5]
54.01
[24.5]
54.01
[24.5]
79.37
[36.0]
79.37
[36.0]
112.44
[51.0]
112.44
[51.0]
Efficiency [%], best
case/typical
1)
97.0/
96.5
97.3/
96.8
98.0/
97.6
97.6/
97.0
97.1/
96.3
97.9/
97.4
97.3/
97.0
98.5/
97.1
97.2/
97.1
97.0 97.1 96.8 97.1 97.1 97.3
Output current
122 °F [50 °C] ambient temperature
Continuous
(3x200–240 V) [A]
1.5 1.9 3.5 6.8 9.6 13.0 19.8 23.0 33.0 41.6 52.4 61.6 80.5 100.1 119
Intermittent
(3x200–240 V) [A]
1.7 2.1 3.9 7.5 10.6 14.3 21.8 25.3 36.3 45.8 57.6 67.8 88.6 110.1 130.9
Table 8.1 3x200–240 V AC, PK25–P45K
1) At rated load conditions
General Specifications and ... Design Guide
106 Danfoss A/S © Rev. 2014-01-14 All rights reserved. MG18C522
88

Table of Contents

Other manuals for Danfoss VLT HVAC Basic Drive FC 101

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Basic Drive FC 101 and is the answer not in the manual?

Danfoss VLT HVAC Basic Drive FC 101 Specifications

General IconGeneral
BrandDanfoss
ModelVLT HVAC Basic Drive FC 101
CategoryDC Drives
LanguageEnglish

Related product manuals