EasyManuals Logo

Danfoss VLT HVAC Basic Drive FC 101 Design Guide

Danfoss VLT HVAC Basic Drive FC 101
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #56 background imageLoading...
Page #56 background image
5 How to Install
5.1 Mechanical Dimensions
5.1.1 Adjustable Frequency Drive Dimensions
A
a
b
B
C
D
130BB614.10
e
f
a
d
e
130BC205.10
e
f
a
e
130BC246.10
Enclosure Power (hp [kW]) Height (in [mm]) Width
(in [mm])
Depth
(in
[mm])
Mounting hole
(in [mm])
Max.
Weight
Frame IP
Class
3x
200–240 V
3x
380–480 V
3x
525–600 V
A
A
1
a B b C d e f lb [kg]
H1 IP20 0.34–2
[0.25–1.5]
0.5–2
[0.37–1.5]
7.68
[195]
10.75
[273]
7.21
[183]
2.95
[75]
2.21
[56]
6.61
[168]
0.35
[9]
0.18
[4.5]
0.21
[5.3]
4.63
[2.1]
H2 IP20 3 [2.2] 3–5
[2.2–4.0]
8.94
[227]
11.93
[303]
8.35
[212]
3.54
[90]
2.56
[65]
7.48
[190]
0.43
[11]
0.22
[5.5]
0.29
[7.4]
7.5
[3.4]
H3 IP20 5 [3.7] 7.5–10
[5.5–7.5]
8.86
[255]
12.95
[329]
9.45
[240]
3.94
[100]
2.91
[74]
8.11
[206]
0.43
[11]
0.22
[5.5]
0.32
[8.1]
9.92
[4.5]
H4 IP20 7.5–10
[5.5–7.5]
15–20
[11–15]
11.65
[296]
14.13
[359]
10.83
[275]
5.32
[135]
4.13
[105]
9.49
[241]
0.5
[12.6]
0.28
[7]
0.33
[8.4]
17.42
[7.9]
H5 IP20 15 [11] 25–30
[18.5–22]
13.15
[334]
15.83
[402]
12.36
[314]
5.91
[150]
4.72
[120]
8.86
[255]
0.5
[12.6]
0.28
[7]
0.34
[8.5]
20.94
[9.5]
H6 IP20 20–25
[15–18.5]
40–60
[30–45]
25–40
[18.5–30]
20.4
[518]
23.43/
25
[595/
635]
(60 hp
[45
kW])
19.50
[495]
9.41
[239]
7.87
[200]
9.53
[242]
- 0.34
[8.5]
0.60
[15]
54.01
[24.5]
H7 IP20 30–40
[22–30]
75–100
[55–75]
50–75
[37–55]
21.65
[550]
24.8/
27.17
[630/
690]
(100 hp
[75
kW])
20.51
[521]
12.32
[313]
10.63
[270]
13.19
[335]
- 0.34
[8.5]
0.68
[17]
79.37
[36]
H8 IP20 50–60
[37–45]
125 [90] 100–125
[75–90]
25.98
[660]
31.5
[800]
24.84
[631]
14.76
[375]
12.99
[330]
13.19
[335]
- 0.34
[8.5]
0.68
[17]
112.44
[51]
H9 IP20 3–10
[2.2–7.5]
10.59
[269]
14.72
[374]
10.12
[257]
5.12
[130]
4.33
[110]
8.07
[205]
15
[11]
0.22
[5.5]
0.35
[9]
14.6
[6.6]
H10 IP20 15–20
[11–15]
15.71
[399]
16.5
[419]
14.96
[380]
6.5
[165]
5.51
[140]
9.76
[248]
0.47
[12]
0.28
[6.8]
0.3
[7.5]
26.46
[12]
How to Install Design Guide
54 Danfoss A/S © Rev. 2014-01-14 All rights reserved. MG18C522
55

Table of Contents

Other manuals for Danfoss VLT HVAC Basic Drive FC 101

Questions and Answers: