7 RS-485 Installation and Set-up
7.1 RS-485
7.1.1 Overview
RS-485 is a two-wire bus interface compatible with multi-
drop network topology, that is, nodes can be connected as
a bus, or via drop cables from a common trunk line. A
total of 32 nodes can be connected to one network
segment.
Repeaters divide network segments.
NOTICE!
Each repeater functions as a node within the segment in
which it is installed. Each node connected within a given
network must have a unique node address across all
segments.
Terminate each segment at both ends using either the
termination switch (S801) of the adjustable frequency
drives or a biased termination resistor network. Always use
shielded twisted pair (STP) cable for bus cabling, and
always follow good common installation practice.
Low-impedance ground connection of the shield at every
node is important, including at high frequencies. Thus,
connect a large surface of the shield to ground, for
example, with a cable clamp or a conductive cable
connector. It may be necessary to apply potential-
equalizing cables to maintain the same ground potential
throughout the network - particularly in installations with
long cables.
To prevent impedance mismatch, always use the same
type of cable throughout the entire network. When
connecting a motor to the adjustable frequency drive,
always use shielded motor cable.
Cable Shielded twisted pair (STP)
Impedance
[Ω]
120
Cable length
(ft [m])
Max. 4,000 ft [1200 m] (including drop lines)
Max. 1,650 ft [500 m] station-to-station
Table 7.1 Cable
7.1.2
Network Connection
Connect the adjustable frequency drive to the RS-485
network as follows (see also Figure 7.1):
1. Connect signal wires to terminal 68 (P+) and
terminal 69 (N-) on the main control board of the
adjustable frequency drive.
2. Connect the cable shield to the cable clamps.
NOTICE!
Shielded, twisted-pair cables are recommended to
reduce noise between conductors.
61 68 69
N
P
COMM. GND
130BB795.10
Figure 7.1 Network Connection
RS-485 Installation and Set... Design Guide
86 Danfoss A/S © Rev. 2014-01-14 All rights reserved. MG18C522
77

Table of Contents

Other manuals for Danfoss VLT HVAC Basic Drive FC 101

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Basic Drive FC 101 and is the answer not in the manual?

Danfoss VLT HVAC Basic Drive FC 101 Specifications

General IconGeneral
BrandDanfoss
ModelVLT HVAC Basic Drive FC 101
CategoryDC Drives
LanguageEnglish

Related product manuals