Current limitations for PM motors:
Currently only supported up to 22 kW
Currently limited to non-salient type PM motors
LC filters not supported together with PM motors
Overvoltage control algorithm is not supported
with PM motors
Kinetic backup algorithm is not supported with
PM motors
Support reduced AMA of the stator resistance Rs
in the system only
No stall detection
No ETR function
2.7.4
Local (Hand On) and Remote (Auto
On) Control
The adjustable frequency drive can be operated manually
via the local control panel (LCP) or remotely via analog/
digital inputs or serial bus. If allowed in 0-40 [Hand on] Key
on LCP, 0-44 [Off/Reset] Key on LCP, and 0-42 [Auto on] Key
on LCP, it is possible to start and stop the adjustable
frequency drive by LCP using the [Hand On] and [Off/
Reset] keys. Alarms can be reset via the [Off/Reset] key.
Hand
On
Off
Reset
Auto
On
130BB893.10
Figure 2.18 LCP Keys
Local reference forces the configuration mode to open-
loop, independent on the setting of 1-00 Configuration
Mode.
Local Reference is restored at power-down.
Product Overview Design Guide
MG18C522 Danfoss A/S © Rev. 2014-01-14 All rights reserved. 27