EasyManuals Logo

Danfoss VLT HVACDrive User Manual

Danfoss VLT HVACDrive
180 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #121 background imageLoading...
Page #121 background image
22-23 No-Flow Function
Common actions for Low Power Detection and Low Speed Detection (Individual selections not possible).
Option: Function:
[0] * OFF
[1] Sleep Mode The drive will enter sleep mode and stop when a No Flow condition is detected. See parameter
group 22-4* for programming options for sleep mode.
[2] Warning The drive will continue to run, but activate a No-Flow Warning [W92]. A drive digital output or a
serial communication bus can communicate a warning to other equipment.
[3] Alarm The drive will stop running and activate a No-Flow Alarm [A 92]. A drive digital output or a serial
communication bus can communicate an alarm to other equipment.
NOTE!
Do not set par. 14-20
Reset Mode
to [13] Infinite auto reset when par. 22-23
No-Flow Function
is set to [3] Alarm. Doing so will cause
the drive to continuously cycle between running and stopping when a No Flow condition is detected.
NOTE!
If the drive is equipped with a constant speed bypass with an automatic bypass function that starts the bypass if the drive experiences
a persistent alarm condition, be sure to disable the bypass’ automatic bypass function, if [3] Alarm is selected as the No-Flow Function.
22-24 No-Flow Delay
Range: Function:
10 s* [1 - 600 s] Set the time. Low Power/Low Speed must remain detected to activate signal for actions. If detection
disappears before the timer runs out, the timer will be reset.
22-26 Dry Pump Function
Select desired action for dry pump operation.
Option: Function:
[0] * OFF
[1] Warning The drive will continue to run, but activate a dry pump warning [W93]. A drive digital output or a
serial communication bus can communicate a warning to other equipment.
[2] Alarm The drive will stop running and activate a dry pump alarm [A93]. A drive digital output or a serial
communication bus can communicate an alarm to other equipment.
[3] The drive will stop running and activate a dry pump alarm [A93]. A drive digital output or a serial
communication bus can communicate an alarm to other equipment.
NOTE!
Low Power Detection
must be Enabled (par. 22-21
Low Power Detection
) and commissioned (using either parameter group 22-3*,
No
Flow Power Tuning
, or par. 22-20
Low Power Auto Set-up
) in order to use Dry Pump Detection.
NOTE!
Do not set par. 14-20
Reset Mode
, to [13] Infinite auto reset, when par. 22-26
Dry Pump Function
is set to [2] Alarm. Doing so will
cause the drive to continuously cycle between running and stopping when a dry pump condition is detected.
VLT
®
HVAC Drive Instruction Manual
7 How to Program the Adjustable Frequency
Drive
MG.11.AB.22 - VLT
®
is a registered Danfoss trademark
7-43
7

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVACDrive and is the answer not in the manual?

Danfoss VLT HVACDrive Specifications

General IconGeneral
BrandDanfoss
ModelVLT HVACDrive
CategoryDC Drives
LanguageEnglish

Related product manuals