8.2 Acoustic Noise or Vibration
If the motor or the equipment driven by the motor, e.g., a fan blade, is making noise or vibrations at certain frequencies, try the following:
Speed Bypass, parameter group 4-6*
Overmodulation, parameter 14-03 set to off
Switching pattern and frequency parameter group 14-0*
Resonance Dampening, parameter 1-64
8 Troubleshooting VLT
®
HVAC Drive Instruction Manual
8-12