22-88 Pressure at Rated Speed
Range: Function:
999999.999
N/A*
[Application dependant] Enter the value corresponding to the Pressure at Rated Speed, in Reference/Feedback Units. This
value can be defined using the pump datasheet.
Please see also
par. 22-82 Work Point Calculation
point A.
22-89 Flow at Design Point
Range: Function:
0.000 N/A* [0.000 - 999999.999 N/A] Enter the value corresponding to the Flow at Design Point. No units necessary.
Please see also
par. 22-82 Work Point Calculation
point C.
22-90 Flow at Rated Speed
Range: Function:
0.000 N/A* [0.000 - 999999.999 N/A] Enter the value corresponding to Flow at Rated Speed. This value can be defined using the pump
datasheet.