5.4.2 ENGINE RUNNING
NOTE: The load transfer signal remains inactive until the Oil Pressure has risen. This
prevents excessive wear on the engine.
In Test Mode
, the load is automatically transferred to the generator.
Once the generator has been placed on load, it is not automatically removed. To manually remove
the load either:
• Press the Manual Mode
button followed by the Open Generator (DSE6110 MKII Only)
or Transfer to Mains
(DSE6120 MKII Only) button.
• Press the Auto Mode
button to return to automatic mode. The set observes all
Auto Mode
start requests and stopping timers before beginning the Auto Mode Stopping
Sequence.
• Press the Stop/Reset Mode button to remove load and stop the generator.
• Activation of an auxiliary input that has been configured to Generator Load Inhibit.
5.4.3 STOPPING SEQUENCE
In Test Mode
the set continues to run until either:
• The Stop/Reset Mode
button is pressed – The delayed load outputs are de-activated
immediately and the set immediately stops.
• The Auto Mode
button is pressed. The set observes all Auto Mode start requests and
stopping timers before beginning the Auto Mode Stopping Sequence.