Operation
Page 63 of 94 057-236 ISSUE: 1
5.4.2 ENGINE RUNNING
NOTE: The load transfer signal remains inactive until the Oil Pressure has risen. This
prevents excessive wear on the engine.
In Test Mode
, the load is automatically transferred to the generator.
Once the generator has been placed on load, it is not automatically removed. To manually remove
the load either:
Press the Manual Mode
button followed by the Open Generator (DSE6110 MKII Only)
or Transfer to Mains
(DSE6120 MKII Only) button.
Press the Auto Mode
button to return to automatic mode. The set observes all
Auto Mode
start requests and stopping timers before beginning the Auto Mode Stopping
Sequence.
Press the Stop/Reset Mode button to remove load and stop the generator.
Activation of an auxiliary input that has been configured to Generator Load Inhibit.
5.4.3 STOPPING SEQUENCE
In Test Mode
the set continues to run until either:
The Stop/Reset Mode
button is pressed – The delayed load outputs are de-activated
immediately and the set immediately stops.
The Auto Mode
button is pressed. The set observes all Auto Mode start requests and
stopping timers before beginning the Auto Mode Stopping Sequence.