Protections
Page 79 of 94 057-236 ISSUE: 1
6.7 MAINTENANCE ALARM
Depending upon module configuration one or more levels of engine maintenance alarm may occur
based upon a configurable schedule.
Example 1
Screen capture from DSE
Configuration Suite Software showing
the configuration of the Maintenance
Alarm for 1, 2 and 3.
When activated, the maintenance
alarm is either a Warning (set
continues to run) or Shutdown
(running the set is not possible).
Resetting the maintenance alarm is
normally actioned by the site service
engineer after performing the required
maintenance.
The method of reset is either by:
Activating an input that has been
configured to Reset Maintenance
Alarm 1, 2 or 3.
Pressing the maintenance reset
button in the DSE Configuration
Suite, Maintenance section.
Example 2
Screen capture from DSE
Configuration Suite Software showing
the configuration of a digital input for
Reset Maintenance Alarm 1.
Example 3
Screen capture from DSE Configuration Suite
Software showing the Maintenance Alarm
Reset ‘button’ in the DSE Configuration Suite
SCADA | MAINTENANCE section.