Operation
Page 65 of 94 057-236 ISSUE: 1
5.5.3 ENGINE RUNNING
NOTE: The load transfer signal remains inactive until the Oil Pressure has risen. This
prevents excessive wear on the engine.
The generator is placed on load if configured to do so.
If all start requests are removed, the stopping sequence begins.
5.5.4 STOPPING SEQUENCE
The Return Delay timer operates to ensure that the starting request has been permanently removed
and isn’t just a short term removal. Should another start request be made during the cooling down
period, the set returns on load.
If there are no starting requests at the end of the Return Delay timer, the load is removed from the
generator to the mains supply and the cooling timer is initiated.
The Cooling Down timer allows the set to run off load and cool sufficiently before being stopped. This
is particularly important where turbo chargers are fitted to the engine.
After the Cooling Down timer has expired, the set is stopped.