Protections
Page 71 of 94 057-236 ISSUE: 1
Fault Description
Fail To Stop
NOTE: Fail to Stop could indicate a faulty oil pressure
sensor. If engine is at rest check oil sensor wiring and
configuration.
The module has detected a condition that indicates that the engine
is running when it has been instructed to stop.
Generator kW Overload
The
measured
kW has risen above the
configured trip level for a
configured duration.
High Fuel Level
The level detected by the fuel level sensor is above the high fuel
level pre-set pre-alarm setting.
Immediate Over Current The measured current has risen above the configured trip level.
Low Fuel Level
The level detected by the fuel level sensor is below the low fuel
level pre-set pre-alarm setting.
Loss Of Speed Sensing Signal
The speed signal from the magnetic pickup is not being received
by the DSE controller.
Maintenance Alarm 1
The module detects that the Maintenance Alarm 1 is due creating
a fault condition, the appropriate LCD message is displayed.
Maintenance Alarm 2
The module detects that the Maintenance Alarm 2 is due creating
a fault condition, the appropriate LCD message is displayed.
Maintenance Alarm 3
The module detects that the Maintenance Alarm 3 is due creating
a fault condition, the appropriate LCD message is displayed.
Oil Pressure Sensor Fault.
The module detects that the circuit to the oil pressure sensor has
been broken.
2130 ID0 Analogue Input E to H
The module detects that an analogue input that has been user
configured to create a fault condition has become active on the
DSE2130 expansion module with ID0.
2130 ID0 Digital Input A to H
The module detects that a digital input that has been user
configured to create a fault condition has become active on the
DSE2130 expansion module with ID0.
2130 ID1 Analogue Input E to H
The module detects that an analogue input that has been user
configured to create a fault condition has become active on the
DSE2130 expansion module with ID1.
2130 ID1 Digital Input A to H
The module detects that a digital input that has been user
configured to create a fault condition has become active on the
DSE2130 expansion module with ID1.