GC-1F Installation Instructions and Reference Handbook
DEIF A/S Page 35 of 123
Mains voltage unbalance detection
The formula for mains voltage unbalance is:
(Most deviating line-to-line voltage - average voltage)*100/average voltage (nominal value in %)
Phase sequence error
Prior to closing a breaker, the unit checks that the phase sequence is correct, depending on the
chosen phase direction in parameter 2280: “phase rotation”. If it is incorrect (reversed), an alarm
will be issued and the breaker in question (generator or option B3 mains breaker) will not be
closed and the breaker’s LED will flash red.
Utility software input configuration
It is possible to configure the inputs indicated in the table. The unit has a number of passive
binary inputs (input terminals 10 to 15).
Input function Comment
Alarm acknowledge Configurable
Start enable (OFF = start blocked) Configurable
Remote start/stop Configurable
Access lock Configurable
Remote manual/auto Configurable
Fire pump (shutdown override) Configurable
D+ (digital running feedback) Configurable
Idle speed Configurable
Test sequence Configurable
GB Pos on Configurable (option G6)
GB Pos off Configurable (option G6)
Digital inputs no. 1 to 6 used as alarms Configurable
Inhibit EI alarms Configurable
Remote Start (pulse) Configurable
Remote Stop (pulse) Configurable
Remote Start and close (pulse) Configurable
Remote Open and stop (pulse) Configurable
EIC increase speed Configurable
EIC decrease speed Configurable
Remote GB open Configurable
Remote GB close Configurable
Island mode Configurable
GB close inhibit Configurable
Input function description
1. Alarm acknowledge
Acknowledges all present alarms.
2. Start enable
This input must be activated to start the engine.
3. Remote start/stop input
Activating this input will start the genset. Deactivating it will stop the genset after cool down
(auto mode only).
4. Access lock
Activating the access lock input deactivates the control push-buttons on the display and the
possibility to change parameters. It will be possible to view measurements, alarms and the
log.

Table of Contents

Other manuals for Deif GC-1F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Deif GC-1F and is the answer not in the manual?

Deif GC-1F Specifications

General IconGeneral
BrandDeif
ModelGC-1F
CategoryController
LanguageEnglish

Related product manuals