GC-1F Installation Instructions and Reference Handbook
DEIF A/S Page 41 of 123
7. Horn
The horn relay is a common alarm output. This means that every time an alarm state ap-
pears, the horn relay will close for the time configured in the parameter 6130 Alarm horn
regardless of fail class. If 6130 is set to 0 seconds, it will be on until the reset horn push-
button is activated or the alarm(s) has (have) been acknowledged.
8. Alarm/limit
When this setting for the relay is selected, the relay can be used in the alarm parameters in
the setting Output A and Output B. This means that with factory settings, the relay 2 can be
used in the parameters as an alarm relay. If the relay is preferred to be a Limit relay, this
selection must be done in the parameter list parameter 5000 to 5060.
9. Fuel pump
Output must be configured to use fuel pump settings.
10. Engine heater
The relay configured to Engine heater will close when the temperature is below the set point in
parameter 6320 and open again when the temperature is above the set point in parameter
6330. For more information, see the description of the function.
11. Stop coil (not acc. in start seq.)
The relay configured to this function will do the same as the normal stop coil with one excep-
tion: It will not close between the start attempts.
12. Generator breaker (continuous)
GB Relay contact will close continuously.
13. GB ON (pulse)
GB relay contact will give an ON pulse signal.
14. GC OFF (pulse)
GB relay contact will give an OFF pulse signal.
15. Manual mode
Mode status signal.
16. Auto mode
Mode status signal.
17. Test mode
Mode status signal.
18. Off mode
Mode status signal.
19. GB status
Contact closed when GB is closed.