Stop sequence
The stop sequence will be activated, if a stop command is given. The stop sequence can include
the cooling down time, if the stop is a normal or controlled stop.
Description Cooling down Stop Comment
Auto mode stop X X
Trip and stop X X
Stop button on display X
Binary shutdown input X
Emergency stop X Engine shutdown and GB opens
Stop command (M-Logic) X
The stop sequence can only be interrupted during the cool down period. Interruptions can occur
in these situations:
Event Comment
Start button is pressed Manual mode only
Engine will run in idle speed if idle is ON
Binary start input Auto mode
GB close button is pressed Manual mode only
Stop failure alarm
A stop failure alarm will occur, if the running feedback (or the generator voltage and frequency)
is still present. The stop failure timer is adjusted in menu 4580. Stop failure will activate the
HORN output, and relay outputs if selected. Factory setting is no relay outputs besides horn.