Table 26. Continuous Operation Specifications for ASHRAE A4
Temperature Specifications
Allowable operations
Temperature range for altitudes <= 900 m (<=
2953 ft)
5 to 45°C (41 to 113°F) with no direct sunlight on the equipment
Humidity percent range (non-condensing at all
times)
8% RH with -12°C minimum dew point to 90% RH with 24°C (75.2°F)
maximum dew point
Operational altitude de-rating Maximum temperature is reduced by 1°C/125 m (1.8°F/410 Ft) above 900
m (2953 Ft)
Table 27. Common Environmental Specifications
Allowable operations
Maximum temperature gradient (applies to both
operation and non-operation)
20°C in an hour* (36°F in an hour) and 5°C in 15 minutes (9°F in 15
minutes), 5°C in an hour* (9°F in an hour) for tape hardware
NOTE: * - Per ASHRAE thermal guidelines for tape hardware, these are
not instantaneous rates of temperature change.
Non-operational temperature limits -40 to 65°C (-40 to 149°F)
Non-operational humidity limits 5% to 95% RH with 27°C (80.6°F) maximum dew point
Maximum non-operational altitude 12,000 meters (39,370 feet)
Maximum operational altitude 3,050 meters (10,006 feet)
Table 28. Maximum vibration specifications
Maximum vibration Specifications
Operating 0.21 G
rms
at 5 Hz to 500 Hz for 10 minutes (all operation orientations)
Storage 1.88 G
rms
at 10 Hz to 500 Hz for 15 minutes (all six sides tested)
Table 29. Maximum shock pulse specifications
Maximum shock pulse Specifications
Operating Six consecutively executed shock pulses in the positive and negative x, y,
and z axis of 6 G for up to 11 ms
Storage Six consecutively executed shock pulses in the positive and negative x, y,
and z axis (one pulse on each side of the system) of 71 G for up to 2 ms
Particulate and gaseous contamination specifications
The following table defines the limitations that help avoid any equipment damage or failure from particulate and gaseous
contamination. If the levels of particulate or gaseous pollution exceed the specified limitations and result in equipment damage
or failure, you may need to rectify the environmental conditions. Remediation of environmental conditions is the responsibility of
the customer.
Table 30. Particulate contamination specifications
Particulate contamination Specifications
Air filtration Data center air filtration as defined by ISO Class 8 per ISO 14644-1
with a 95% upper confidence limit
NOTE: This condition applies to data center environments only. Air
filtration requirements do not apply to IT equipment designed to be
used outside a data center, in environments such as an office or
factory floor.
Technical specifications 33