Table 30. Particulate contamination specifications(continued)
Particulate contamination Specifications
NOTE: Air entering the data center must have MERV11 or MERV13
filtration.
Conductive dust Air must be free of conductive dust, zinc whiskers, or other
conductive particles
NOTE: This condition applies to data center and non-data center
environments.
Corrosive dust
Air must be free of corrosive dust
Residual dust present in the air must have a deliquescent point less
than 60% relative humidity
NOTE: This condition applies to data center and non-data center
environments.
Table 31. Gaseous contamination specifications
Gaseous contamination Specifications
Copper coupon corrosion rate <300 Å/month per Class G1 as defined by ANSI/ISA71.04-2013
Silver coupon corrosion rate <200 Å/month as defined by ANSI/ISA71.04-2013
Thermal restriction matrix
Table 32. Label reference
Label Description
STD Standard performance
HPR Gold High performance (gold grade)
EXT. HSK. External Heat sink
LP Low profile
FH Full height
DLC Direct liquid cooling
Table 33. Air cooling: Thermal restriction matrix (non-GPU)
Configuration
No
BP
8 x 2.5-
inch U.2
4 x 3.5-inch 10 x 2.5-inch SAS
10 x 2.5-inch
NVMe
16 x E3.S
14 x E3.S
8 x E3.S
Rear storage No
Rear
Drive
s
No Rear
Drives
No
Rear
Drive
s
E3.S
x 2
No
Rear
Drives
2.5-
inch
SAS
x 2
E3.S
x 2
No
Rear
Drives
E3.S
x 2
No Rear
Drives
cTDP Model
Core
Count
CPU
TDP/
cTDP
240
W
9334 32 35°C 35°C 35°C 30°C 35°C 35°C 35°C 35°C 35°C 35°C
240
W
9224 24 35°C 35°C 35°C 30°C 35°C 35°C 35°C 35°C 35°C 35°C
240
W
9254 24 35°C 35°C 35°C 30°C 35°C 35°C 35°C 35°C 35°C 35°C
240
W
9124 16 35°C 35°C 35°C 30°C 35°C 35°C 35°C 35°C 35°C 35°C
34 Technical specifications