8.5.6 NE
FB/FC Explanation
Applicable
model
FC
NE is used for a not-equal comparison of two variables or constants. DVP15MC11T
Parameters
Parameter
name
Meaning
Input/
Output
Description Valid range
In1
Comparison
data
Input A value to compare
Depends on the data type of the variable
that the input parameter is connected to.
In2
Comparison
data
Input A value to compare
Depends on the data type of the variable
that the input parameter is connected to.
Out
Comparison
result
Output Comparison result
Depends on the data type of the variable
that the output parameter is connected
to.
Boolean
Bit string Integer
Real
number
Time, date
String
BOOL
BYTE
WORD
DWORD
LWORD
USINT
UINT
UDINT
ULINT
SINT
INT
DINT
LINT
REAL
LREAL
TIME
DATE
TOD
DT
STRING
In1
and
In2
Out
Note:
The symbol indicates that the parameter is allowed to connect to the variable or constant of the data type.
Function Explanation
NE is used for a not-equal comparison of two variables and constants. Out is TRUE if In1ǂIn2.
Otherwise, Out is FALSE.
The input parameters In1 and In2 are allowed to be the variables of different data types in this
instruction when the data types of input variables are not BOOL, TIME, DATE, TOD and STRING.
When the data type of one input variable is one of BOOL, TIME, DATE, TOD and STRING, input
parameters In1 and In2 are both required to be of the data type. For example, if the data type of In1
is TIME, the data type of In2 must be TIME. Otherwise, an error will occur in the compiling of the
software.
Precautions for Correct Use
The input variables are not allowed to omit. An error will occur during the compiling of the software if
any input variable is omitted. But the output variable is allowed to omit.
The data type of output variables must be BOOL. Otherwise, an error will occur during the compiling
of the software.
NE
EN ENO
In1 Out
In2
8-38

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta Electronics DVP15MC11T and is the answer not in the manual?

Delta Electronics DVP15MC11T Specifications

General IconGeneral
BrandDelta Electronics
ModelDVP15MC11T
CategoryController
LanguageEnglish

Related product manuals